CVE-2023-2186
HighCVSS 8.2Exploitation Probability (EPSS)
Elevated risk53th percentile - higher than 53% of all known CVEs
Summary
On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format string characters to perform unrestricted memory reads. This can repeatedly crash the GTWWebMonitor.exe process to cause DoS, and an authenticated user can leverage the vulnerability to leak memory from the process, potentially leading to code execution.
Risk Assessment
The vulnerability can be exploited by an unauthenticated attacker to cause denial of service (DoS) and by an authenticated user to leak sensitive memory contents, which in an exploit chain could lead to code execution and system compromise.
Recommendation
Update SCADA Data Gateway to a version later than v5.01.03 if available, or apply compensating controls such as restricting network access to the service and monitoring for malformed broadcast messages.
Other vulnerabilities in SCADA Data Gateway
Original NVD description (English source)
On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format string characters to the SCADA Data Gateway to perform unrestricted memory reads.An unauthenticated user can use this format string vulnerability to repeatedly crash the GTWWebMonitor.exe process to DoS the Web Monitor. Furthermore, an authenticated user can leverage this vulnerability to leak memory from the GTWWebMonitor.exe process. This could be leveraged in an exploit chain to gain code execution.
Vulnerability data from NVD (NIST) · CISA KEV · EPSS